Skip to Main Content
Search distributed energy resources in New York

NYU Langone Medical Center

Overview NYU Langone Medical Center

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Jul 2017 to Mar 2021
186
GWh
electricity generated
Capacity
Factor
2,140
MMcf
generator fuel consumed
Electric
Efficiency
1,652
BBtu
heat used
Thermal
Efficiency
938
MMcf
HRSG fuel consumed
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Jul 2017 to Mar 2021
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 186,148 3,077,898 1,652,319 0 58.3 28.8 52.0 72.0
Jul 2017
3,294 43,618 20,257 0 45.1 27.3 45.0 70.0
Aug 2017
2,645 33,910 15,525 0 36.2 27.5 44.4 70.2
Sep 2017
3,183 40,577 16,972 0 45.0 27.7 40.5 66.5
Oct 2017
3,866 50,105 21,079 0 52.9 27.7 40.8 66.3
Nov 2017
2,920 43,532 19,588 0 41.3 28.6 43.6 65.8
Dec 2017
5,138 84,608 40,714 0 70.3 30.6 46.6 66.7
Jan 2018
4,416 76,730 35,372 0 60.4 29.0 44.7 63.7
Feb 2018
4,740 73,426 34,131 0 71.8 29.6 45.0 66.4
Mar 2018
5,058 82,119 41,144 0 69.2 30.3 48.5 68.9
Apr 2018
1,917 31,602 14,902 0 27.1 26.8 45.7 65.8
May 2018
3,080 45,626 20,681 0 42.2 28.2 43.9 66.3
Jun 2018
4,139 64,608 30,845 0 58.5 28.1 46.3 67.4
Jul 2018
3,576 59,047 29,973 0 48.9 28.7 49.2 69.2
Aug 2018
4,635 76,888 38,127 0 63.4 27.7 48.0 68.0
Sep 2018
4,627 76,719 37,707 0 65.4 27.0 47.6 67.6
Oct 2018
3,743 61,391 29,366 0 51.2 27.0 46.4 66.5
Nov 2018
4,042 64,968 29,419 0 57.2 27.9 43.9 64.5
Dec 2018
5,059 84,195 40,386 0 69.2 27.7 46.5 66.4
Jan 2019
4,893 92,009 48,770 0 67.0 27.5 51.4 68.9
Feb 2019
4,222 76,013 38,915 0 64.0 27.5 49.6 68.0
Mar 2019
4,989 82,309 40,820 0 68.3 28.3 48.1 68.1
Apr 2019
2,715 41,877 18,559 0 38.4 26.3 42.9 64.4
May 2019
4,164 59,184 25,203 0 57.0 27.3 41.3 64.5
Jun 2019
5,067 83,871 45,096 0 71.7 32.5 52.1 72.1
Jul 2019
4,642 85,520 45,274 0 63.5 27.9 51.3 69.2
Aug 2019
4,330 72,817 38,618 0 59.3 31.1 51.4 71.1
Sep 2019
5,207 86,492 48,821 0 73.6 32.8 54.7 74.6
Oct 2019
3,735 61,492 37,537 0 51.1 30.0 59.2 79.2
Nov 2019
5,301 85,781 52,647 0 75.0 32.3 59.5 79.9
Dec 2019
5,177 87,393 52,176 0 70.9 31.7 57.9 77.4
Jan 2020
5,080 91,299 55,148 0 69.5 29.3 58.5 76.9
Feb 2020
4,413 81,964 49,924 0 64.6 27.4 59.0 76.8
Mar 2020
4,602 79,112 47,816 0 63.0 27.6 58.6 77.8
Apr 2020
423 12,376 7,078 0 6.0 14.9 55.4 66.7
May 2020
3,774 65,233 38,871 0 51.6 28.1 57.7 76.9
Jun 2020
4,814 78,609 47,616 0 68.1 30.6 58.7 78.9
Jul 2020
4,204 79,450 48,838 0 57.5 26.4 59.6 77.1
Aug 2020
4,387 78,080 46,256 0 60.0 26.7 57.4 76.0
Sep 2020
4,835 79,460 46,719 0 68.4 27.9 57.0 77.1
Oct 2020
3,979 62,806 35,976 0 54.5 28.9 55.5 76.5
Nov 2020
3,592 61,227 40,148 0 50.8 27.8 63.5 82.9
Dec 2020
4,814 81,613 52,491 0 65.9 29.3 62.3 81.8
Jan 2021
5,271 90,371 52,175 0 72.1 30.6 55.9 75.2
Feb 2021
4,785 85,232 50,666 0 72.5 31.2 57.6 76.2
Mar 2021
2,658 42,641 23,973 0 75.2 31.9 54.5 75.1

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The HRSG monthly summary table provides measured data and key performance indicators for the heat recovery steam generator (HRSG).

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

HRSG Summary Table

Jul 2017 to Mar 2021
Steam Heat Used (MMBtu) Hot Water Heat Used (MMBtu) Total Heat Used (MMBtu) Generator Fuel Consumed (Mcf) HRSG Fuel Consumed (Mcf) Total Fuel Consumed (Mcf) Thermal Efficiency (% HHV)
Total 1,652,319 0 1,652,319 2,140,268 937,630 3,077,898 52.0
Jul 2017
20,257 0 20,257 39,931 3,686 43,618 45.0
Aug 2017
15,525 0 15,525 31,793 2,117 33,910 44.4
Sep 2017
16,972 0 16,972 38,048 2,529 40,577 40.5
Oct 2017
21,079 0 21,079 46,174 3,931 50,105 40.8
Nov 2017
19,588 0 19,588 33,784 9,748 43,532 43.6
Dec 2017
40,714 0 40,714 55,477 29,131 84,608 46.6
Jan 2018
35,372 0 35,372 50,281 26,448 76,730 44.7
Feb 2018
34,131 0 34,131 53,043 20,383 73,426 45.0
Mar 2018
41,144 0 41,144 55,136 26,983 82,119 48.5
Apr 2018
14,902 0 14,902 23,685 7,917 31,602 45.7
May 2018
20,681 0 20,681 36,085 9,540 45,626 43.9
Jun 2018
30,845 0 30,845 48,775 15,833 64,608 46.3
Jul 2018
29,973 0 29,973 41,149 17,898 59,047 49.2
Aug 2018
38,127 0 38,127 55,369 21,519 76,888 48.0
Sep 2018
37,707 0 37,707 56,631 20,088 76,719 47.6
Oct 2018
29,366 0 29,366 45,818 15,573 61,391 46.4
Nov 2018
29,419 0 29,419 47,844 17,124 64,968 43.9
Dec 2018
40,386 0 40,386 60,407 23,788 84,195 46.5
Jan 2019
48,770 0 48,770 58,797 33,212 92,009 51.4
Feb 2019
38,915 0 38,915 50,826 25,187 76,013 49.6
Mar 2019
40,820 0 40,820 58,375 23,935 82,309 48.1
Apr 2019
18,559 0 18,559 34,122 7,756 41,877 42.9
May 2019
25,203 0 25,203 50,497 8,687 59,184 41.3
Jun 2019
45,096 0 45,096 51,540 32,331 83,871 52.1
Jul 2019
45,274 0 45,274 55,037 30,483 85,520 51.3
Aug 2019
38,618 0 38,618 46,116 26,701 72,817 51.4
Sep 2019
48,821 0 48,821 52,542 33,950 86,492 54.7
Oct 2019
37,537 0 37,537 41,139 20,352 61,492 59.2
Nov 2019
52,647 0 52,647 54,287 31,494 85,781 59.5
Dec 2019
52,176 0 52,176 53,960 33,433 87,393 57.9
Jan 2020
55,148 0 55,148 57,428 33,871 91,299 58.5
Feb 2020
49,924 0 49,924 53,283 28,681 81,964 59.0
Mar 2020
47,816 0 47,816 55,058 24,054 79,112 58.6
Apr 2020
7,078 0 7,078 9,352 3,025 12,376 55.4
May 2020
38,871 0 38,871 44,382 20,851 65,233 57.7
Jun 2020
47,616 0 47,616 52,003 26,606 78,609 58.7
Jul 2020
48,838 0 48,838 52,687 26,763 79,450 59.6
Aug 2020
46,256 0 46,256 54,294 23,785 78,080 57.4
Sep 2020
46,719 0 46,719 57,224 22,236 79,460 57.0
Oct 2020
35,976 0 35,976 45,556 17,250 62,806 55.5
Nov 2020
40,148 0 40,148 42,667 18,560 61,227 63.5
Dec 2020
52,491 0 52,491 54,277 27,337 81,613 62.3
Jan 2021
52,175 0 52,175 56,995 33,375 90,371 55.9
Feb 2021
50,666 0 50,666 50,804 34,428 85,232 57.6
Mar 2021
23,973 0 23,973 27,589 15,052 42,641 54.5

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
NYU Langone Medical Center 72.0 % 52.0 % 28.8 % 58.3 % 186,148 MWh
Top Peer 52.5 % 28.1 % 28.5 % 64.8 % 59,934 MWh
Average Peer 47.9 % 25.3 % 25.8 % 62.0 % 63,185 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Large (1000+ kW)
  • Facility Category: Health Care (Inpatient)
  • Total Peers in Group: 4

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Jul 2017 to Mar 2021
Peak Demand Reduction (kWP)
6,198
kW
Total Generation (kWhA)
186,147,684
kWh
Heat Recovered
1,652,319
MMBtu
Gas Consumed
3,077,898
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

85.0
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

80.0
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.