Skip to Main Content
Search distributed energy resources in New York

The Crossing

Overview 1962-66 1st Ave

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Oct 2024 to Nov 2025
575
MWh
electricity generated
Capacity
Factor
8,088
Mcf
generator fuel consumed
Electric
Efficiency
1,038
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Oct 2024 to Nov 2025
Electricity Generated (kWh) Total Fuel Consumed (cf) Total Heat Used (MBtu) Heat Rejected (MBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 574,995 8,088,097 1,037,944 4,818,140 10.5 23.5 12.4 35.9
Oct 2024
25,933 364,410 19,731 226,475 9.2 23.5 5.2 28.8
Nov 2024
31,714 450,461 82,615 213,588 7.9 23.3 17.8 41.1
Dec 2024
55,536 777,826 97,232 422,267 13.3 23.6 12.1 35.7
Jan 2025
59,663 836,112 90,885 416,153 14.3 23.6 10.5 34.1
Feb 2025
52,334 733,691 137,997 369,222 13.9 23.6 18.2 41.8
Mar 2025
37,441 498,649 104,930 240,377 9.0 24.8 20.4 45.2
Apr 2025
15,036 202,762 14,502 118,104 3.7 24.5 6.9 31.5
May 2025
39,396 531,777 34,127 344,580 9.5 24.5 6.2 30.7
Jun 2025
29,562 429,916 42,074 291,327 7.3 22.7 9.5 32.2
Jul 2025
24,002 322,730 30,621 202,783 5.8 24.6 9.2 33.8
Aug 2025
58,834 844,107 81,170 586,041 14.1 23.1 9.3 32.4
Sep 2025
59,071 843,830 90,243 618,557 14.7 23.2 10.4 33.5
Oct 2025
47,936 690,088 106,144 420,443 11.5 23.0 14.9 37.9
Nov 2025
38,537 561,738 105,674 348,225 13.7 22.7 18.2 40.9

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
The Crossing 35.9 % 12.4 % 23.5 % 10.5 % 574,995 kWh
Top Peer 69.9 % 41.9 % 28.0 % 22.3 % 404,051 kWh
Average Peer 51.1 % 25.8 % 25.3 % 29.8 % 734,135 kWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Medium (250-1000 kW)
  • Facility Category: Residential
  • Total Peers in Group: 14

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Oct 2024 to Nov 2025
Peak Demand Reduction (kWP)
60
kW
Total Generation (kWhA)
574,995
kWh
Heat Recovered
1,038
MMBtu
Gas Consumed
8,088
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

39.1
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

39.9
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.