Aug 2019 to Aug 2023
4,310
MWh
electricity generated
Capacity
Factor
59,151
Mcf
generator fuel consumed
Electric
Efficiency
21,863
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Aug 2019 to Aug 2023
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 4,310 59,151 21,863 11,020 15.3 24.1 35.8 59.9
Aug 2019
82 1,008 571 2 33.0 26.8 54.9 81.6
Sep 2019
148 1,812 859 87 25.9 27.1 45.9 73.0
Oct 2019
185 2,334 346 1,248 31.2 26.2 14.4 40.5
Nov 2019
171 2,190 483 1,244 29.9 25.8 21.4 47.2
Dec 2019
132 1,731 878 213 22.3 25.2 49.1 74.3
Jan 2020
190 2,508 1,313 159 32.1 25.0 50.7 75.8
Feb 2020
172 2,295 1,269 66 31.1 24.8 53.6 78.3
Mar 2020
138 1,775 919 203 23.3 25.7 50.2 75.9
Apr 2020
0 0 0 0 0.0 0.0 0.0 0.0
May 2020
107 1,315 289 619 18.1 27.0 21.3 48.3
Jun 2020
20 260 98 68 3.6 25.9 36.5 62.4
Jul 2020
178 2,636 1,047 347 30.2 22.4 38.5 60.9
Aug 2020
189 2,249 680 573 31.9 27.7 29.3 57.0
Sep 2020
62 766 134 360 10.9 26.9 17.0 43.8
Oct 2020
108 1,386 294 558 18.3 25.9 20.5 46.4
Nov 2020
175 2,356 716 721 30.6 24.6 29.4 54.0
Dec 2020
162 2,143 1,037 131 27.3 24.9 46.9 71.8
Jan 2021
139 1,865 987 26 23.5 24.7 51.2 75.9
Feb 2021
141 1,910 990 33 26.5 24.5 50.2 74.7
Mar 2021
38 510 154 180 6.4 24.5 29.3 53.8
Apr 2021
146 1,955 613 583 25.5 24.7 30.4 55.0
May 2021
172 2,230 648 678 29.1 25.5 28.2 53.7
Jun 2021
210 2,637 957 432 36.6 26.3 35.2 61.5
Jul 2021
195 2,390 582 645 33.0 27.0 23.6 50.6
Aug 2021
259 3,217 1,411 131 43.8 26.6 42.5 69.2
Sep 2021
227 2,882 1,246 117 39.6 26.0 41.9 67.9
Oct 2021
105 1,455 554 223 17.8 23.9 36.9 60.8
Nov 2021
47 684 211 218 8.2 22.7 29.9 52.5
Dec 2021
0 0 0 0 0.0 0.0 0.0 0.0
Jan 2022
0 0 0 0 0.0 0.0 0.0 0.0
Feb 2022
0 0 0 0 0.0 0.0 0.0 0.0
Mar 2022
0 0 0 0 0.0 0.0 0.0 0.0
Apr 2022
64 894 376 204 11.3 23.8 40.8 64.6
May 2022
160 2,112 789 503 27.0 25.0 36.2 61.2
Jun 2022
93 1,532 499 159 16.3 20.1 31.6 51.7
Jul 2022
2 83 32 1 0.4 9.4 37.6 47.0
Aug 2022
40 1,414 512 12 6.8 9.3 35.1 44.4
Sep 2022
11 1,204 134 10 1.9 3.0 10.8 13.8
Oct 2022
41 1,044 236 266 7.0 13.1 21.9 35.0
Nov 2022
0 2 0 0 0.0 0.0 0.0 0.0
Dec 2022
0 136 0 0 0.0 0.0 0.0 0.0
Jan 2023
0 229 0 0 0.0 0.0 0.0 0.0
Feb 2023
0 < 1 0 0 0.0 0.0 0.0 0.0
Mar 2023
0 0 0 0 0.0 0.0 0.0 0.0
Apr 2023
0 0 0 0 0.0 0.0 0.0 0.0
May 2023
0 0 0 0 0.0 0.0 0.0 0.0
Jun 2023
0 0 0 0 0.0 0.0 0.0 0.0
Jul 2023
0 0 0 0 0.0 0.0 0.0 0.0
Aug 2023
0 0 0 0 0.0 0.0 0.0 0.0

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
New York Towers 59.9 % 35.8 % 24.1 % 15.3 % 4,310 MWh
Top Peer 73.0 % 46.6 % 26.5 % 52.6 % 7,079 MWh
Average Peer 50.4 % 25.2 % 25.2 % 29.0 % 2,333 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Medium (250-1000 kW)
  • Facility Category: Residential
  • Total Peers in Group: 28

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Aug 2019 to Aug 2023
Peak Demand Reduction (kWP)
160
kW
Total Generation (kWhA)
4,310,098
kWh
Heat Recovered
21,863
MMBtu
Gas Consumed
59,151
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

68.9
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

66.6
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.