Skip to Main Content
Search distributed energy resources in New York

One North Fourth

Overview 1 North 4th Place

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Apr 2018 to Aug 2023
3,964
MWh
electricity generated
Capacity
Factor
69,332
Mcf
generator fuel consumed
Electric
Efficiency
7,415
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Apr 2018 to Aug 2023
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 3,964 69,332 7,415 0 41.8 18.9 10.4 29.3
Apr 2018
32 417 31 0 21.9 25.0 7.2 32.3
May 2018
101 1,474 76 0 67.8 22.6 5.0 27.6
Jun 2018
86 1,528 66 0 59.7 18.6 4.2 22.8
Jul 2018
53 1,059 59 0 35.6 16.5 5.4 21.9
Aug 2018
54 1,090 67 0 36.6 16.5 5.9 22.4
Sep 2018
85 1,601 111 0 58.8 17.5 6.7 24.2
Oct 2018
98 1,756 134 0 65.9 18.5 7.4 25.8
Nov 2018
104 1,801 156 0 72.5 19.2 8.4 27.6
Dec 2018
108 1,932 187 0 72.5 18.5 9.4 27.8
Jan 2019
103 1,807 221 0 69.4 18.9 11.8 30.7
Feb 2019
13 221 29 0 9.6 19.3 12.5 31.8
Mar 2019
< 1 11 0 0 < 0.1 3.5 0.0 3.5
Apr 2019
< 1 9 0 0 < 0.1 3.8 0.0 3.8
May 2019
< 1 8 0 0 < 0.1 4.1 0.0 4.1
Jun 2019
< 1 5 0 0 < 0.1 5.2 0.0 5.2
Jul 2019
< 1 < 1 0 0 < 0.1 8.0 0.0 8.0
Aug 2019
< 1 2 0 0 < 0.1 5.4 0.0 5.4
Sep 2019
< 1 8 0 0 < 0.1 3.8 0.0 3.8
Oct 2019
< 1 10 0 0 < 0.1 4.3 0.0 4.3
Nov 2019
< 1 10 0 0 < 0.1 3.1 0.0 3.1
Dec 2019
< 1 13 0 0 < 0.1 1.3 0.0 1.3
Jan 2020
< 1 13 0 0 < 0.1 2.9 0.0 2.9
Feb 2020
< 1 5 0 0 < 0.1 3.5 0.0 3.5
Mar 2020
75 1,124 103 0 50.3 22.0 8.9 30.9
Apr 2020
102 1,563 129 0 71.0 21.6 8.0 29.6
May 2020
88 1,360 85 0 59.4 21.5 6.0 27.6
Jun 2020
91 1,429 98 0 63.4 21.1 6.6 27.8
Jul 2020
105 1,554 99 0 70.5 22.3 6.2 28.5
Aug 2020
105 1,618 246 0 70.4 21.4 14.8 36.2
Sep 2020
101 1,574 258 0 70.4 21.3 15.9 37.1
Oct 2020
65 1,016 166 0 43.4 21.0 15.9 36.9
Nov 2020
100 1,601 257 0 69.5 20.7 15.6 36.2
Dec 2020
82 1,302 13 0 55.4 20.9 1.0 21.9
Jan 2021
76 1,215 99 0 51.3 20.8 7.9 28.7
Feb 2021
84 1,330 255 0 62.9 21.0 18.6 39.6
Mar 2021
106 1,698 281 0 71.1 20.6 16.1 36.7
Apr 2021
101 1,640 238 0 69.9 20.3 14.1 34.4
May 2021
0 1 0 0 0.0 0.0 0.0 0.0
Jun 2021
57 942 145 0 39.4 19.9 15.0 34.9
Jul 2021
97 1,668 250 0 65.4 19.3 14.6 33.9
Aug 2021
61 1,017 165 0 41.0 19.9 15.7 35.6
Sep 2021
68 1,198 191 0 46.9 18.6 15.4 34.1
Oct 2021
54 1,040 223 0 36.3 17.2 20.7 37.9
Nov 2021
62 1,181 281 0 43.3 17.5 23.0 40.5
Dec 2021
63 1,197 291 0 42.1 17.3 23.5 40.9
Jan 2022
62 1,197 286 0 41.9 17.2 23.1 40.3
Feb 2022
65 1,181 219 0 48.0 18.1 18.0 36.1
Mar 2022
77 1,392 184 0 52.0 18.4 12.8 31.2
Apr 2022
34 623 79 0 23.9 18.3 12.3 30.6
May 2022
81 1,482 87 0 58.5 18.2 5.7 23.9
Jun 2022
88 1,600 < 1 0 60.9 18.1 0.0 18.1
Jul 2022
72 1,289 0 0 48.1 18.4 0.0 18.4
Aug 2022
49 892 12 0 32.6 18.0 1.3 19.3
Sep 2022
76 1,496 58 0 52.8 16.8 3.8 20.6
Oct 2022
79 1,468 < 1 0 53.1 17.8 0.0 17.8
Nov 2022
65 1,235 79 0 44.9 17.3 6.2 23.5
Dec 2022
65 1,209 92 0 43.4 17.7 7.4 25.1
Jan 2023
68 1,297 41 0 45.7 17.4 3.1 20.4
Feb 2023
79 1,510 78 0 59.0 17.4 5.0 22.4
Mar 2023
67 1,281 145 0 44.7 17.2 10.9 28.1
Apr 2023
74 1,480 231 0 51.5 16.6 15.1 31.7
May 2023
80 1,586 242 0 53.5 16.6 14.8 31.4
Jun 2023
73 1,468 205 0 50.5 16.4 13.5 29.9
Jul 2023
61 1,236 171 0 42.5 16.4 13.4 29.8
Aug 2023
67 1,360 193 0 48.4 16.4 13.8 30.2

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
One North Fourth 29.3 % 10.4 % 18.9 % 41.8 % 3,964 MWh
Top Peer 87.4 % 58.2 % 29.2 % 54.8 % 91 MWh
Average Peer 57.5 % 34.7 % 22.8 % 34.8 % 1,253 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Small (0-250 kW)
  • Facility Category: Residential
  • Total Peers in Group: 96

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Apr 2018 to Aug 2023
Peak Demand Reduction (kWP)
94
kW
Total Generation (kWhA)
3,963,592
kWh
Heat Recovered
7,415
MMBtu
Gas Consumed
69,332
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

31.9
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

32.5
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.