Skip to Main Content
Search distributed energy resources in New York

The Michelangelo Hotel New York

Overview 761-779 7TH Ave Condominium - Michaelangelo Hotel

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Dec 2018 to Jul 2022
1,411
MWh
electricity generated
Capacity
Factor
19,259
Mcf
generator fuel consumed
Electric
Efficiency
6,091
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Dec 2018 to Jul 2022
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 1,411 19,259 6,091 5,477 17.0 24.2 30.6 54.9
Dec 2018
22 294 81 77 34.2 24.3 26.5 50.9
Jan 2019
99 1,407 376 413 50.3 23.3 25.9 49.2
Feb 2019
82 1,214 299 278 46.2 22.4 23.9 46.3
Mar 2019
73 1,065 283 272 37.1 22.7 25.8 48.5
Apr 2019
43 602 167 165 22.4 23.5 26.9 50.4
May 2019
45 576 168 188 22.6 25.6 28.3 53.9
Jun 2019
106 1,358 246 329 55.6 25.8 17.5 43.4
Jul 2019
81 1,014 222 285 41.2 26.5 21.2 47.7
Aug 2019
120 1,541 289 384 60.7 25.7 18.2 43.9
Sep 2019
103 1,373 413 484 53.7 24.7 29.2 53.9
Oct 2019
142 1,826 619 622 72.1 25.7 32.8 58.6
Nov 2019
93 1,306 590 398 48.5 23.4 43.8 67.3
Dec 2019
83 1,184 557 329 42.0 23.1 45.6 68.7
Jan 2020
90 1,284 493 414 45.5 23.1 37.2 60.3
Feb 2020
96 1,324 654 357 51.9 23.9 47.9 71.7
Mar 2020
70 1,016 439 308 35.7 22.9 41.9 64.8
Apr 2020
0 0 0 0 0.0 0.0 0.0 0.0
May 2020
0 0 0 0 0.0 0.0 0.0 0.0
Jun 2020
0 0 0 0 0.0 0.0 0.0 0.0
Jul 2020
0 0 0 0 0.0 0.0 0.0 0.0
Aug 2020
0 0 0 0 0.0 0.0 0.0 0.0
Sep 2020
0 0 0 0 0.0 0.0 0.0 0.0
Oct 2020
0 0 0 0 0.0 0.0 0.0 0.0
Nov 2020
0 0 0 0 0.0 0.0 0.0 0.0
Dec 2020
0 0 0 0 0.0 0.0 0.0 0.0
Jan 2021
0 0 0 0 0.0 0.0 0.0 0.0
Feb 2021
1 24 0 0 0.6 14.5 0.0 14.5
Mar 2021
0 0 0 0 0.0 0.0 0.0 0.0
Apr 2021
0 0 0 0 0.0 0.0 0.0 0.0
May 2021
0 0 0 0 0.0 0.0 0.0 0.0
Jun 2021
0 0 0 0 0.0 0.0 0.0 0.0
Jul 2021
0 0 0 0 0.0 0.0 0.0 0.0
Aug 2021
0 0 0 0 0.0 0.0 0.0 0.0
Sep 2021
0 0 0 0 0.0 0.0 0.0 0.0
Oct 2021
0 0 0 0 0.0 0.0 0.0 0.0
Nov 2021
0 0 0 0 0.0 0.0 0.0 0.0
Dec 2021
0 0 0 0 0.0 0.0 0.0 0.0
Jan 2022
0 0 0 0 0.0 0.0 0.0 0.0
Feb 2022
0 0 0 0 0.0 0.0 0.0 0.0
Mar 2022
0 0 0 0 0.0 0.0 0.0 0.0
Apr 2022
0 0 0 0 0.0 0.0 0.0 0.0
May 2022
0 0 0 0 0.0 0.0 0.0 0.0
Jun 2022
11 159 38 32 5.8 23.0 23.1 46.1
Jul 2022
52 692 157 141 41.2 25.0 22.0 47.0

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
The Michelangelo Hotel New York 54.9 % 30.6 % 24.2 % 17.0 % 1,411 MWh
Top Peer 34.8 % 7.2 % 27.5 % 52.0 % 4,267 MWh
Average Peer 48.2 % 24.9 % 23.3 % 39.8 % 5,287 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Medium (250-1000 kW)
  • Facility Category: Lodging
  • Total Peers in Group: 5

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Dec 2018 to Jul 2022
Peak Demand Reduction (kWP)
153
kW
Total Generation (kWhA)
1,411,104
kWh
Heat Recovered
6,091
MMBtu
Gas Consumed
19,259
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

62.5
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

61.0
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.