Skip to Main Content
Search distributed energy resources in New York

Dorchester Towers

Overview Dorchester Towers

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Oct 2020 to Dec 2023
3,337
MWh
electricity generated
Capacity
Factor
43,707
Mcf
generator fuel consumed
Electric
Efficiency
17,617
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Oct 2020 to Dec 2023
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 3,337 43,707 17,617 7,665 31.9 25.3 39.1 64.3
Oct 2020
0 0 < 1 < 1 0.0 0.0 0.0 0.0
Nov 2020
10 0 25 254 3.9 0.0 0.0 0.0
Dec 2020
46 299 162 514 16.4 50.6 52.4 103.0
Jan 2021
98 1,131 522 171 35.1 28.6 44.7 73.4
Feb 2021
110 1,260 637 92 43.5 28.8 49.0 77.8
Mar 2021
119 1,374 684 118 42.8 28.7 48.2 77.0
Apr 2021
100 1,172 580 92 36.9 28.1 47.9 76.0
May 2021
88 1,056 420 194 31.7 27.7 38.5 66.2
Jun 2021
155 1,838 485 572 57.2 27.8 25.6 53.4
Jul 2021
168 1,991 443 703 60.1 27.8 21.6 49.4
Aug 2021
155 1,849 370 685 55.7 27.8 19.4 47.2
Sep 2021
90 1,074 304 280 33.3 27.7 27.5 55.1
Oct 2021
66 774 345 98 23.5 28.0 43.2 71.2
Nov 2021
77 886 431 66 28.5 28.7 47.2 75.9
Dec 2021
96 1,125 533 93 34.3 28.1 45.9 74.0
Jan 2022
97 1,137 524 111 34.9 28.4 44.7 73.0
Feb 2022
90 1,043 509 76 35.6 28.4 47.2 75.6
Mar 2022
133 1,545 770 89 47.7 28.5 48.3 76.7
Apr 2022
126 1,459 721 93 46.7 28.6 47.9 76.5
May 2022
87 1,026 457 87 31.1 28.0 43.2 71.1
Jun 2022
86 1,058 472 117 31.9 26.9 43.2 70.2
Jul 2022
74 882 348 150 26.4 27.6 38.2 65.8
Aug 2022
110 1,319 399 346 39.5 27.7 29.3 57.0
Sep 2022
154 1,844 417 619 57.1 27.6 21.9 49.6
Oct 2022
120 1,401 628 144 43.0 28.3 43.4 71.7
Nov 2022
128 1,491 729 55 47.5 28.4 47.4 75.8
Dec 2022
73 1,680 818 74 26.1 14.3 47.2 61.5
Jan 2023
26 969 448 62 9.4 9.0 44.8 53.8
Feb 2023
0 1,026 481 62 0.0 0.0 45.4 45.4
Mar 2023
32 1,129 532 65 11.5 9.4 45.6 55.1
Apr 2023
102 1,238 602 67 37.9 27.3 47.1 74.5
May 2023
73 882 418 363 26.1 27.3 45.9 73.2
Jun 2023
81 1,007 375 138 29.8 26.4 36.1 62.5
Jul 2023
77 957 257 253 27.5 26.6 26.0 52.6
Aug 2023
72 875 222 242 25.6 27.1 24.6 51.7
Sep 2023
91 1,106 285 311 33.6 27.1 25.0 52.1
Oct 2023
43 571 231 52 15.5 25.1 39.2 64.2
Nov 2023
57 1,547 703 116 21.3 12.3 44.0 56.3
Dec 2023
29 686 328 40 10.3 13.9 46.3 60.2

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
Dorchester Towers 64.3 % 39.1 % 25.3 % 31.9 % 3,337 MWh
Top Peer 63.4 % 20.9 % 42.5 % 9.2 % 1,036 MWh
Average Peer 50.2 % 25.1 % 25.1 % 28.7 % 2,011 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Medium (250-1000 kW)
  • Facility Category: Residential
  • Total Peers in Group: 27

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Oct 2020 to Dec 2023
Peak Demand Reduction (kWP)
141
kW
Total Generation (kWhA)
3,337,187
kWh
Heat Recovered
17,617
MMBtu
Gas Consumed
43,707
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

74.1
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

71.5
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.