Skip to Main Content
Search distributed energy resources in New York

Hudson Yards New York

Overview Hudson Yards Tower C

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Apr 2018 to Aug 2023
41,564
MWh
electricity generated
Capacity
Factor
624,665
Mcf
generator fuel consumed
Electric
Efficiency
72,037
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Apr 2018 to Aug 2023
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 41,564 624,665 72,037 0 73.1 22.0 11.2 33.2
Apr 2018
250 4,012 172 0 28.9 20.6 4.1 24.8
May 2018
690 11,409 104 0 77.3 20.0 0.9 20.9
Jun 2018
628 10,693 713 0 72.7 19.4 6.5 25.9
Jul 2018
589 9,953 1,112 0 66.0 19.6 10.8 30.4
Aug 2018
582 9,614 1,109 0 65.2 20.0 11.2 31.2
Sep 2018
602 9,516 696 0 69.7 20.9 7.1 28.0
Oct 2018
643 9,886 551 0 72.1 21.5 5.4 26.9
Nov 2018
699 10,899 515 0 80.9 21.2 4.6 25.8
Dec 2018
762 12,188 516 0 85.4 20.7 4.1 24.8
Jan 2019
775 12,494 745 0 86.8 20.5 5.8 26.3
Feb 2019
691 11,184 600 0 85.7 20.4 5.2 25.6
Mar 2019
705 11,297 593 0 79.0 20.7 5.1 25.7
Apr 2019
514 8,175 403 0 59.5 20.8 4.8 25.6
May 2019
674 11,273 516 0 75.5 19.8 4.4 24.2
Jun 2019
643 10,984 1,930 0 74.4 19.3 17.0 36.4
Jul 2019
632 10,579 1,124 0 70.8 19.7 10.3 30.0
Aug 2019
569 8,726 2,460 0 63.8 21.6 27.3 48.9
Sep 2019
611 9,344 2,435 0 70.7 21.6 25.3 46.9
Oct 2019
649 9,193 816 0 72.7 23.4 8.6 32.0
Nov 2019
669 9,331 854 0 77.5 23.7 8.9 32.6
Dec 2019
629 8,688 1,373 0 70.5 23.9 15.3 39.3
Jan 2020
597 8,481 1,666 0 66.9 23.3 19.0 42.3
Feb 2020
634 8,910 1,579 0 75.9 23.5 17.2 40.7
Mar 2020
728 10,136 1,681 0 81.6 23.8 16.1 39.8
Apr 2020
705 9,905 1,559 0 81.6 23.5 15.2 38.8
May 2020
713 10,443 1,071 0 79.9 22.6 9.9 32.5
Jun 2020
655 10,034 499 0 75.8 21.6 4.8 26.4
Jul 2020
641 10,227 2,452 0 71.8 20.7 23.2 44.0
Aug 2020
620 9,838 2,743 0 69.4 20.8 27.0 47.9
Sep 2020
635 9,578 276 0 73.5 21.9 2.8 24.7
Oct 2020
716 10,469 306 0 80.2 22.6 2.8 25.4
Nov 2020
703 10,256 1,065 0 81.4 22.7 10.1 32.7
Dec 2020
754 10,574 1,524 0 84.5 23.6 14.0 37.6
Jan 2021
628 8,819 1,214 0 70.4 23.6 13.3 36.9
Feb 2021
567 7,812 2,017 0 70.3 24.0 25.0 49.0
Mar 2021
735 10,413 2,030 0 82.3 23.3 18.9 42.2
Apr 2021
643 9,088 1,725 0 74.4 23.4 18.4 41.8
May 2021
605 8,726 1,425 0 67.8 22.9 15.8 38.8
Jun 2021
570 8,569 911 0 65.9 22.0 10.3 32.3
Jul 2021
574 8,771 795 0 64.3 21.7 8.8 30.4
Aug 2021
573 8,866 824 0 64.1 21.4 9.0 30.4
Sep 2021
591 9,217 868 0 68.4 21.2 9.1 30.3
Oct 2021
537 8,162 1,059 0 60.1 21.8 12.6 34.3
Nov 2021
741 10,599 2,006 0 85.7 23.1 18.3 41.5
Dec 2021
759 10,860 2,426 0 85.0 23.1 21.6 44.8
Jan 2022
747 10,562 2,401 0 83.6 23.4 22.0 45.4
Feb 2022
638 8,847 2,188 0 79.1 23.8 24.0 47.8
Mar 2022
739 10,564 2,320 0 82.7 23.1 21.3 44.4
Apr 2022
690 9,928 2,202 0 79.9 23.0 21.5 44.5
May 2022
665 9,865 1,346 0 79.6 22.3 13.2 35.5
Jun 2022
615 9,205 745 0 71.2 22.1 7.8 29.9
Jul 2022
523 8,131 604 0 58.6 21.3 7.2 28.5
Aug 2022
563 8,621 300 0 63.1 21.6 3.4 25.0
Sep 2022
528 7,890 416 0 61.1 22.1 5.1 27.2
Oct 2022
529 7,587 1,096 0 59.3 23.1 14.0 37.1
Nov 2022
620 8,931 1,660 0 71.8 23.0 18.0 41.0
Dec 2022
727 10,388 2,362 0 81.4 23.1 22.0 45.2
Jan 2023
759 10,927 1,340 0 85.0 23.0 11.9 34.9
Feb 2023
647 9,293 0 0 80.3 23.0 0.0 23.0
Mar 2023
760 10,998 < 1 0 85.1 22.9 0.0 22.9
Apr 2023
724 10,672 0 0 83.8 22.4 0.0 22.4
May 2023
657 9,716 0 0 73.6 22.4 0.0 22.4
Jun 2023
552 8,371 0 0 63.9 21.8 0.0 21.8
Jul 2023
549 8,471 0 0 63.6 21.4 0.0 21.4
Aug 2023
497 7,507 0 0 59.5 21.9 0.0 21.9

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
Hudson Yards New York 33.2 % 11.2 % 22.0 % 73.1 % 41,564 MWh
Top Peer 43.4 % 6.8 % 36.6 % 27.3 % 4,239 MWh
Average Peer 41.6 % 10.2 % 31.5 % 30.0 % 13,002 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Large (1000+ kW)
  • Facility Category: Office
  • Total Peers in Group: 4

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Apr 2018 to Aug 2023
Peak Demand Reduction (kWP)
893
kW
Total Generation (kWhA)
41,563,611
kWh
Heat Recovered
72,037
MMBtu
Gas Consumed
624,665
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

36.0
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

36.9
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.