Skip to Main Content
Search distributed energy resources in New York

1199 Housing

Overview 2070-2080 Housing Corporation 2100 1st Avenue Building BC Building D

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Dec 2022 to Mar 2025
2,556
MWh
electricity generated
Capacity
Factor
31,170
Mcf
generator fuel consumed
Electric
Efficiency
8,117
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Dec 2022 to Mar 2025
Electricity Generated (MWh) Total Fuel Consumed (Mcf) Total Heat Used (MMBtu) Heat Rejected (MMBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 2,556 31,170 8,117 0 24.5 27.1 25.2 52.4
Dec 2022
< 1 3 0 0 < 0.1 9.8 0.0 9.8
Jan 2023
0 0 0 0 0.0 0.0 0.0 0.0
Feb 2023
74 952 0 0 20.9 25.8 0.0 25.8
Mar 2023
0 0 0 0 0.0 0.0 0.0 0.0
Apr 2023
0 0 0 0 0.0 0.0 0.0 0.0
May 2023
0 0 0 0 0.0 0.0 0.0 0.0
Jun 2023
0 0 0 0 0.0 0.0 0.0 0.0
Jul 2023
12 156 6 0 3.1 26.1 3.7 29.8
Aug 2023
22 340 12 0 5.7 21.7 3.4 25.1
Sep 2023
128 1,478 70 0 33.6 28.7 4.6 33.3
Oct 2023
173 2,009 114 0 43.7 28.4 5.5 33.9
Nov 2023
105 1,534 300 0 27.5 22.7 19.0 41.6
Dec 2023
139 1,536 450 0 35.3 30.0 28.4 58.3
Jan 2024
175 1,994 646 0 44.4 29.1 31.4 60.4
Feb 2024
160 1,845 628 0 43.3 28.6 33.0 61.6
Mar 2024
156 1,851 618 0 39.7 28.0 32.3 60.3
Apr 2024
120 1,538 547 0 31.6 25.9 34.5 60.4
May 2024
94 1,236 452 0 23.9 25.2 35.4 60.6
Jun 2024
84 1,053 382 0 21.9 26.3 35.2 61.5
Jul 2024
83 1,059 371 0 21.0 25.9 34.0 59.8
Aug 2024
78 1,111 366 0 19.8 23.2 31.9 55.1
Sep 2024
108 1,372 448 0 28.4 26.1 31.6 57.7
Oct 2024
164 1,956 464 0 41.5 27.7 23.0 50.6
Nov 2024
169 1,995 424 0 44.2 28.0 20.6 48.6
Dec 2024
142 1,667 496 0 36.0 28.1 28.8 57.0
Jan 2025
167 2,012 598 0 42.4 27.5 28.8 56.3
Feb 2025
147 1,812 520 0 41.3 26.8 27.8 54.6
Mar 2025
55 660 205 0 33.2 27.5 30.1 57.6

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
1199 Housing 52.4 % 25.2 % 27.1 % 24.5 % 2,556 MWh
Top Peer 24.3 % 6.9 % 17.4 % 44.2 % 2,095 MWh
Average Peer 46.9 % 22.8 % 24.1 % 25.8 % 1,461 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Medium (250-1000 kW)
  • Facility Category: Residential
  • Total Peers in Group: 25

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Dec 2022 to Mar 2025
Peak Demand Reduction (kWP)
160
kW
Total Generation (kWhA)
2,556,211
kWh
Heat Recovered
8,117
MMBtu
Gas Consumed
31,170
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

58.7
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

58.2
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.