Skip to Main Content
Search distributed energy resources in New York

Taxi 30-02 39th Street

Overview Taxi 30-02 39th Street

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Apr 2020 to Aug 2021
683
MWh
electricity generated
Capacity
Factor
8,259
Mcf
generator fuel consumed
Electric
Efficiency
4,624
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Apr 2020 to Aug 2021
Electricity Generated (kWh) Total Fuel Consumed (cf) Total Heat Used (MBtu) Heat Rejected (MBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 683,062 8,259,333 4,623,824 1,541,435 29.5 27.4 54.2 81.6
Apr 2020
13,392 159,000 77,687 7,150 34.9 27.9 47.3 75.2
May 2020
40,614 556,000 266,195 81,882 27.3 24.2 46.4 70.6
Jun 2020
32,932 602,333 267,779 151,489 22.9 18.1 43.1 61.2
Jul 2020
38,894 650,000 272,374 101,141 26.1 19.8 40.6 60.4
Aug 2020
34,725 576,000 244,884 102,371 23.3 19.9 41.2 61.1
Sep 2020
17,878 279,000 126,631 77,111 12.4 21.2 44.0 65.2
Oct 2020
33,999 502,333 232,567 149,492 22.8 22.4 44.9 67.2
Nov 2020
48,171 657,000 311,596 107,262 33.5 24.2 46.0 70.2
Dec 2020
63,018 829,333 421,333 63,830 42.4 25.1 49.2 74.4
Jan 2021
76,405 905,000 462,336 25,745 51.3 27.9 49.5 77.4
Feb 2021
74,496 890,333 452,550 24,900 55.4 27.7 49.3 76.9
Mar 2021
46,973 613,000 308,000 40,220 31.6 25.3 48.7 74.0
Apr 2021
41,803 575,000 272,340 112,629 29.0 24.0 45.9 69.9
May 2021
29,716 455,000 255,652 288,089 20.0 21.6 54.4 76.0
Jun 2021
35,349 4,000 258,832 94,064 24.5 2922.6 6270.2 9192.7
Jul 2021
36,050 2,000 260,884 78,172 24.2 5961.2 12639.7 18600.9
Aug 2021
18,645 4,000 132,183 35,887 22.8 1541.5 3202.1 4743.7

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
Taxi 30-02 39th Street 81.6 % 54.2 % 27.4 % 29.5 % 683,062 kWh
Top Peer 88.7 % 66.5 % 22.2 % 26.0 % 236,154 kWh
Average Peer 59.5 % 36.8 % 22.7 % 34.7 % 424,045 kWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Small (0-250 kW)
  • Facility Category: Residential
  • Total Peers in Group: 79

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Apr 2020 to Aug 2021
Peak Demand Reduction (kWP)
72
kW
Total Generation (kWhA)
683,062
kWh
Heat Recovered
4,624
MMBtu
Gas Consumed
8,259
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

95.2
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

90.7
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.