Skip to Main Content
Search distributed energy resources in New York

The Promenade

Overview The Promenade

The project snapshot page provides a quick overview of the performance of the DER project. Hover over individual key performance indicators to see a definition.

Performance Snapshot

Nov 2019 to Aug 2021
1,112
MWh
electricity generated
Capacity
Factor
14,759
Mcf
generator fuel consumed
Electric
Efficiency
7,520
MMBtu
heat used
Thermal
Efficiency
CHP
Efficiency

The project monthly summary table provides measured data and key performance indicators for the DER project.

To view data for another date range, select your desired months and press “Go”.

To download data from the monthly summary table in CSV format, press the download button to the top right of the table.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Summary Table

Nov 2019 to Aug 2021
Electricity Generated (kWh) Total Fuel Consumed (cf) Total Heat Used (MBtu) Heat Rejected (MBtu) Capacity Factor (%) Electric Efficiency (% HHV) Thermal Efficiency (% HHV) CHP Efficiency (% HHV)
Total 1,111,540 14,758,730 7,519,834 1,738,982 71.7 24.9 49.4 74.3
Nov 2019
37,862 482,020 282,472 30,195 79.0 26.0 56.8 82.8
Dec 2019
60,649 770,770 459,249 44,720 81.5 26.0 57.7 83.8
Jan 2020
56,903 726,440 432,490 45,819 76.5 25.9 57.7 83.6
Feb 2020
57,389 737,830 445,304 39,621 82.5 25.7 58.5 84.2
Mar 2020
60,850 789,477 478,602 44,011 81.8 25.5 58.7 84.2
Apr 2020
56,312 741,743 444,883 44,006 78.2 25.1 58.1 83.2
May 2020
50,971 665,810 379,284 38,981 68.5 25.3 55.2 80.5
Jun 2020
52,415 672,710 391,888 46,969 72.8 25.8 56.4 82.2
Jul 2020
52,384 692,530 377,924 60,008 70.4 25.0 52.9 77.9
Aug 2020
53,677 727,830 385,767 64,506 72.1 24.4 51.4 75.7
Sep 2020
45,552 627,040 340,066 51,012 63.3 24.0 52.6 76.6
Oct 2020
52,818 700,877 341,550 98,358 71.0 24.9 47.2 72.1
Nov 2020
53,976 701,880 328,654 107,634 75.0 25.4 45.4 70.8
Dec 2020
56,753 732,950 366,597 84,062 76.3 25.6 48.5 74.1
Jan 2021
52,850 681,350 354,397 62,529 71.0 25.7 50.4 76.1
Feb 2021
50,125 650,320 343,598 55,206 74.6 25.5 51.2 76.7
Mar 2021
40,216 540,370 280,198 53,486 54.1 24.6 50.2 74.9
Apr 2021
42,991 639,080 234,824 158,816 59.7 22.2 35.6 57.9
May 2021
50,296 753,490 228,059 195,697 67.6 22.1 29.3 51.4
Jun 2021
46,091 662,460 220,907 160,507 64.0 23.0 32.3 55.3
Jul 2021
53,519 706,883 266,967 169,297 71.9 25.0 36.6 61.6
Aug 2021
26,940 354,870 136,152 83,543 65.9 25.1 37.2 62.3

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The monthly summary plot shows monthly sums of measured data and monthly averages of key performance indicators.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly summary plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The time series plot shows averages of measured data and key performance indicators. The plot can be switched between the daily and hourly time steps, to adjust the level of averaging displayed.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the time series plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed

Times are shown in Eastern Time (ET) and are adjusted to reflect Daylight Saving Time (DST).

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

Data Displayed:

The ambient temperature plot shows averages of measured data and key performance indicators versus ambient temperature.

To view data for another date range or time step, select your desired dates and time step and press “Go”. Due to performance constraints, hourly data may only be displayed within a date range of up to one month in length.

To download data used to create the ambient temperature plot in CSV format, press the download button to the top right of the chart.

Automated data filtering can be enabled or disabled via the control. Filtered data automatically checks to determine if the energy streams measured are consistent with each other (e.g. fuel consumption or heat recovery are reported only when a DER is reporting generated power). Disabling this control shows all data available.

Click on legend entries below the plot, if present, to show or hide data.

Data Displayed
Ambient Temperature data provided by NOAA at weather.govLink opens in new window - close new window to return to this page.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.

The project performance benchmark page shows how the DER project performs compared to similar-sized projects using the same technology in the same facility category. The key performance index used for benchmarking can be changed by selecting the desired rating from the table headings at the bottom of the page. Clicking on each result in the distribution will bring up the name and link to other related facilities.

To view data for another date range, select your desired months and press “Go”.

Note that benchmarking only occurs on data with automated data filtering on, to ensure consistent ranking results.

CHP
Efficiency
Thermal
Efficiency
Electric
Efficiency
Capacity
Factor
Electric
Generation
The Promenade 74.3 % 49.4 % 24.9 % 71.7 % 1,112 MWh
Top Peer — % 59.1 % 46.0 % 5.0 % 83 MWh
Average Peer 61.2 % 37.8 % 23.4 % 33.7 % 516 MWh

Peer Criteria

  • Technology: CHP
  • Generation Capacity: Small (0-250 kW)
  • Facility Category: Residential
  • Total Peers in Group: 86

The project monthly CHP performance rating plot shows overall CHP performance and highlights periods for potential performance improvement.

To view data for another date range, select your desired months and press “Go”.

To download data used to create the monthly CHP performance rating plot in CSV format, press the download button to the top right of the chart.

Note that rating only occurs on data with automated data filtering on, to ensure consistent ranking results.

The peak demand reduction shows the contribution of the CHP system to reducing the utility grid peak demand, and other calculations that were utilized in previous NYSERDA CHP performance programs. The peak demand reduction (kWP) is defined as the average CHP output during the period spanning May 1 through October 31, Monday through Friday, 12:00 Noon to 6:00 PM. Federal holidays are excluded from this period.

The total generation (kWhA) is defined as the total net CHP generation during the period evaluated.

The two CHP efficiencies (FCECHP) are program specific, and differ slightly from the conventional CHP efficiency.

The 2013 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 1,032 BTU/CF HHV, however the useful heat recovery is divided by a displaced boiler efficiency of 80%.

The 2010 CHP systems manual defines FCECHP as the combined net electrical and useful heat recovery divided by the fuel input at 928 BTU/CF LHV. No displaced boiler efficiency is assumed in the FCECHP calculation.

CHP Performance Program Metrics

Nov 2019 to Aug 2021
Peak Demand Reduction (kWP)
73
kW
Total Generation (kWhA)
1,111,540
kWh
Heat Recovered
7,520
MMBtu
Gas Consumed
14,759
Mcf
FCECHP

FCECHP 2013 =
[(WG × 3.413) + (QU / 0.8)] / [FG × 1.032]

86.6
% HHV
FCECHP

FCECHP 2006–2010 =
[(WG × 3.413) + QU] / [FG × 0.928]

82.5
% LHV

Use this page to download all measured performance data for a DER project in CSV format. Select your desired date range and time step, then press the “Download” button to save the data file to your computer.

Download Data

To download performance data, select your desired date range and time step, then click the Download button.

Production data is not in real time and may be delayed as data is periodically reported and uploaded to this website.